Overall Review F3348
The module is automatically tested during operation. The main test routines are:
– Reading back of the output signals. The operating point of the 0-signal read back is
≤ 6.5 V. Up to this value the level of the 0-signal may arise in case of a fault and this will
not be detected
– Switching capability of test signal and cross-talking (walking-bit test).
Outputs 500 mA, short-circuit proof
Internal voltage drop max. 2 V at 500 mA load
Admissible line resistance (in + out) max. 11 Ω
Operating point for
short-circuit current 0.6…1.0 A
Output leakage current max. 200 µA
Output voltage if output is reset max. 1.5 V
Monitored switching time max. 200 µs
Space requirement 4 SU
Operating data 5 VDC / 100 mA
48 VDC / 100 mA plus load
(supply via cable plug)
For submit your review, you should login to your account. If you buy this product before, your review submit as product owner.
Add New Review